A closed chilled water loop should not lose water – in practice it does, through vents, pump seals and make-up. Every litre of make-up dilutes inhibitor, which is why dose has to be maintained, not set once.
The Operating Reality
A commercial or industrial chilled water loop serves air handling units, process coolers and fan coils from a central chiller plant, with a make-up line and a dosing pot or skid.
Why Manual Dosing Falls Short
Dilution and oxygen ingress drive corrosion; warm return temperatures drive biological growth. Inhibitor concentration that drifts below the protection band shows up as fouled coils and a rising approach temperature.
How Automatic Chemical Dosing Fits
- Automatic feed keeps inhibitor inside the protection band continuously, removing the saw-tooth of manual top-up.
- Conductivity and pH feedback let the controller detect make-up-driven dilution and respond on its own.
- Leak alarm within 2 seconds and dry-running protection suit plant rooms that are visited only weekly.
Selection Checklist
- Define the control signal first (pH, ORP, conductivity or flow-proportional) before sizing the pump.
- Size the metering pump to the lowest expected dose with margin, not to the peak dose.
- Confirm chemical compatibility of wetted parts (316L, PVC, PVDF) with every product to be fed.
- Provide containment, leak detection and dry-running protection in the dosing room design.
- Integrate the skid with PLC, DCS or remote telemetry so dose is visible in the control room.
Related Products
- Automatic Chemical Dosing System
- Automatic Condenser Tube Cleaning System (ATCS)
- Constant Pressure Water Make-up System
FAQ
Related Dosing Guides
Explore more in our Chemical Dosing Systems →

Pingback: Sistema Automático de Dosificación Química para HVAC y Agua Industrial | HyApexFlow
Pingback: نظام الجرعات الكيميائية الأوتوماتيكي لأنظمة التدفئة والتهوية وتكييف الهواء والمياه الصناعية | HyApexFlow
Pingback: Système de dosage chimique automatique pour le CVC et l'eau industrielle | HyApexFlow